Online-Monitoring UPS & Battery Sizing

Tick the analysers in your monitoring cabinet, set the hold-up time, and get the UPS VA rating and battery Ah that will actually ride through the outage — lead-acid DoD, C-rate discharge and tropical temperature included. For QCVN 08:2023 / PERMENLHK data-continuity stations.

1Cabinet load

Tick each device and set the count. Watts marked * are "per spec book" — the tools treat them as estimates until confirmed. Intermittent loads (pump, heater) are entered at their duty factor.
Total real load— W

Results — UPS & battery

UPS rating needed
VA
Battery (bank V)
Ah
Discharge C-rate
C
ItemValueBasis

2Battery options (nearest standard)

OptionHolds (h)Runtime
Standard VRLA blocks: 7 / 9 / 12 / 18 / 26 / 40 / 65 Ah. Runtime = bank Wh × DoD × η × discharge-eff ÷ load. C-rate efficiency from the discharge table (0.6C/1 h → 0.6; 0.2C/4 h → 0.8; 0.1C/9 h → 0.9) [4][5].

Station bill

ItemSpec

Quote this station at factory price

Analysers and UPS hardware at the manufacturer's ex-works price — our margin comes solely from the export tax rebate. Batteries are bought locally (transport rule); this sheet gives the Ah and the tropical 2-year replacement note behind that purchase.

Request a quote for this duty ← I&C Unit 3: range selector
Response within 24 hours · Inputs stay in your browser — nothing is uploaded.

Sources & parameter basis

[1]Rack Battery / AZCalculator UPS battery calc — VA=W/pf, Ah=P·T/(V·η·DoD), lead-acid 50 % DoD, temp comp 3 %/°C.
[2]calculator.city UPS sizing — margin 15–30 %, pf 0.8 typical, watts vs VA.
[3]jscalc UPS runtime — usable Wh = V·Ah·DoD·η; Peukert warning.
[4]ups88.cn battery calc — output pf 0.7, load at 70–80 % of rating, η≈0.9, C-rate discharge efficiency table, worked 38 Ah example.
[5]Industry C-rate discharge efficiency table (0.6C/1 h → 0.6 … 0.1C/9 h → 0.9).
[6]Jiuyuhub product data — PH6000C/PH3000C <3 W published; other loads per spec book (estimates flagged).
Full derivation and worked example: Online-Monitoring-UPS-Calculation-Sheet.md (Unit 4 of the I&C manual).