| [1] | I/O design practice — 10-20 % spare on PLC I/O cards; analog 8-ch, AO 4-ch, DI/DO 16-ch module sizing; 32-unit-load limit per RS-485 segment (Unit 2). |
| [2] | Hazardous-area (biogas/H₂S) wiring — intrinsically-safe (IS) barriers add a barrier drop per loop and 3-wire field runs; loop power budget in Unit 1. |
| [3] | Signal mapping — PH6000C pH+ORP = 2 AI (or 1 Modbus node); DO6000Y / MS6000SG / NT6000G / CON6000C = 1 AI (or 1 node); SE10A = 1 AI + 1 pulse DI (or 1 node); S3000L / S3000CG·CD = 1 AI. |
| [4] | Actuator mapping — pump 1 DO + 1 DI (fault); on/off valve 1 DO (modulating → 1 AO); dosing pump LM80C/TS600 1 DO + 1 AI (speed FB); CTL-IO-AIO 2 AI + 1 AO; UV skid 1 DI. |
| [5] | Jiuyuhub product data — PH6000C, DO6000Y, MS6000SG, NT6000G, CON6000C, SE10A, S3000L, S3000CG·CD, CTL-IO-AIO, LM80C/TS600, LW-10 (RS-485 surge) in stock. |