Design ManualInstrumentation & control › RS-485 / Modbus bus
FREE ENGINEERING TOOL · I&C UNIT 2

RS-485 / Modbus RTU Bus Design

Will your online instruments actually talk to the PLC at the end of that trunk? Length-vs-baud field limits, propagation-delay check, daisy-chain & stub rules, 120 Ω termination, unit-load count — and IEC 61643-21 surge protection with LW-10 placement for thunderstorm sites. Built for Southeast-Asian plants.

1Bus parameters

2Site & surge

Results — will the bus talk?

Field limit @baud
m
Verdict
Round-trip / bit
bit
CheckValueLimit / ruleStatus
BaudNominalQuiet fieldNoisy fieldYour run

Surge & instrumentation bill

ItemQtyNote

Quote this bus's instruments at factory price

RS-485 analysers and LW-10 signal surge protectors at the manufacturer's ex-works price — our margin comes solely from the export tax rebate. Termination and 120 Ω STP cable are bought locally; this sheet gives the numbers behind that purchase.

Request a quote for this duty ← I&C Unit 1: loop & cable sizing
Response within 24 hours · Inputs stay in your browser — nothing is uploaded.

Sources & parameter basis

[1]TIA/EIA-485-A — 32 unit loads, 1200 m, common-mode −7…+12 V.
[2]TI SLLA272 — unit-load definition; 1/8-UL transceivers → 256 nodes.
[3]Modbus over Serial Line Specification — nominal 1200 m, daisy chain.
[4]Industrial Monitor Direct Modbus RS-485 guide — field length-vs-baud table (halving per doubling), stub <1 m, termination & bias.
[5]Innovatic RS-485 engineering note — length ≈ 1200/(1+(kBaud/250)²)^½; stub capacitance 300/kBaud nF.
[6]Modbus RTU wiring guide — Belden 9841-class cable, bias 560–1000 Ω.
[7]THOR TRSS-485 / CITEL DLC signal SPD datasheets — IEC 61643-21, classes D1/C2.
[8]RS485 SPD installation & selection guide — Uc matching, In ≥5 kA, PE lead <0.5 m, SPD/shield earth separation.
Full derivation and worked examples: RS485-Bus-Design-Calculation-Sheet.md (Unit 2 of the I&C manual).
Questions about a duty, a specification, or transparent sourcing? Contact our application engineers →